-40%
Micrologic 6.0a schneider-electric circuit breaker controller AAV73102 33073
$ 675.84
- Description
- Size Guide
Description
Masterpactproduct name
Micrologic
product or component type
Control unit
range compatibility
Masterpact NT06...16
Masterpact NW08...40
Masterpact NW40b...63
device application
Distribution
poles description
3P
4P
protected poles description
4t
3t
3t + N/2
network type
AC
network frequency
50/60 Hz
trip unit name
Micrologic 6.0 A
trip unit technology
Electronic
trip unit protection functions
Selective + earth-fault protection
protection type
Earth fault
Overload protection (long time)
Short time short-circuit protection
Instantaneous short-circuit protection
trip unit rating
630 A at 50 °C
800 A at 50 °C
1000 A at 50 °C
1250 A at 50 °C
1600 A at 50 °C
2000 A at 50 °C
2500 A at 50 °C
3200 A at 50 °C
4000 A at 50 °C
5000 A at 50 °C
6300 A at 50 °C
Complementary
mounting mode
Fixed
Drawout
long time pick-up adjustment type Ir
Adjustable 9 settings
long time pick-up adjustment range
0.4...1 x In
long time delay adjustment type
Adjustable 9 settings
[tr] long-time delay adjustment range
0.7…16.6 s 7.2 x Ir
0.7…24 s 6 x Ir
12.5…600 s 1.5 x Ir
thermal memory
20 mn
short-time pick-up adjustment type Isd
Adjustable 9 settings
[Isd] short-time pick-up adjustment range
1.5...10 x Ir
short-time delay adjustment type
Adjustable
[tsd] short-time delay adjustment range
0…0.4 s I²t=off
0.1…0.4 s I²t=on
instantaneous pick-up adjustment type Ii
Adjustable 9 settings
instantaneous pick-up adjustment range
2...15 x In
Off
ground-fault pick-up adjustment type
Adjustable 9 settings
[Ig] ground-fault pick-up adjustment range
0.2...1 x In for 400 A < In < 1250 A
0.3...1 x In for In <= 400 A
500...1200 A for In >= 1250 A
ground-fault time delay adjustment type -tg
Adjustable
[tg] ground-fault time delay adjustment range
0…0.4 s I²t=off
0.1…0.4 s I²t=on
zone selective interlocking ZSI
With
communication of data
Measurement readout
Protection and alarm settings
display type
Digital display
type of measurement
Ammeter
Environment
ambient air temperature for operation
-25…70 °C
ambient air temperature for storage
-25…85 °C
Contractual warranty
Warranty
18 months